日本地球惑星科学連合2016年大会

講演情報

口頭発表

セッション記号 S (固体地球科学) » S-TT 計測技術・研究手法

[S-TT51] 地震観測・処理システム

2016年5月23日(月) 10:45 〜 12:00 102 (1F)

コンビーナ:*中村 洋光(防災科学技術研究所)、座長:篠原 雅尚(東京大学地震研究所)

11:30 〜 11:45

[STT51-04] 日本海溝海底地震津波観測網(S-net) ~陸上局システムについて~

*植平 賢司1金沢 敏彦1望月 将志1藤本 博己1野口 伸一1眞保 敬1汐見 勝彦1功刀 卓1青井 真1松本 拓己1関口 渉次1篠原 雅尚2山田 知朗2 (1.防災科学技術研究所、2.東京大学地震研究所)

キーワード:日本海溝海底地震津波観測網(S-net)

Seafloor Observation Network for Earthquakes and Tsunamis along the Japan Trench (S-net) project to construct a large-scale seafloor network of cable-linked observatories is in progress around Japan Trench and Kuril Trench in Japan. The S-net consists of 150 ocean bottom earthquake and tsunami observation stations, ocean bottom fiber optic cables which are about 5,700 km in total length, landing stations, IP-VPN network which delivers data to data centers, and data centers. The ocean bottom fiber optic cables connect the observation stations to land, and they are drawn inside landing stations.

We have constructed five landing stations; Minamiboso station in Minamiboso City, Chiba Pref., Kashima station in Kashima City, Ibaraki Pref., Watari station in Watari Town, Miyagi Pref., Miyako station in Miyako City, Iwate Pref., and Hachinohe station in Hachinohe City, Aomori Pref.. The Watari station is located on the third floor of reinforced concrete building, and other stations are container-type data centers.
In the landing station, there are a high voltage receiving transformer equipment, an emergency diesel generator with a tank which can store fuel for one week, uninterruptible power supplies (UPSs), a power feed equipment (PFE) that supplies constant DC current (1.1 A) to a submarine cable and observation units, optical receiver transmission equipment, optical wavelength division multiplexing equipment (WDM), GPS clocks, data conversion servers, data transmission servers, supervisory equipment, and so on.

In each earthquake and tsunami observatory under sea water, there installed two sets of three component servo accelerometers, a set of three component velocity seismometers (analog outputs), and two quartz type depth sensors and a set of three-component quartz type accelerometers (frequency outputs). These data are transmitted to the landing stations as the digital data which synchronized to a GPS clock signal supplied from the landing station. The data of frequency outputs are frequency count values at sampling frequency of 8 kHz, and these of analog outputs are digitized values by 24 bits AD converter at sampling frequency of 1 kHz. Data conversion servers at the landing station receive these data. The 8 kHz frequency count data are converted into physical value data of 100 Hz (acceleration) or 10 Hz (water pressure and temperature), and these physical data are delivered to data transmission servers. The 1 kHz digitized analog data are converted into 100 Hz data by decimation filter, and delivered to data transmission servers.

The data received by data transmission servers will be transmit to Tsukuba data center, Tokyo backup data center, Japan Metrological Agency (JMA), and related institutions via two control center using an IP-VPN network.