10:15 AM - 10:30 AM
[2O04] Development of evaluation methods for High Energy Arcing Faults (HEAF)
(2) Study of oxidation model for Cu vapor
Keywords:High Energy Arcing Faults, HEAF, Cu vapor, Hydraulic Analysis, CFD, Ansys Fluent, Thermal Radiation
Thermal fluid analysis of metal vapor is important because metal vapor generated during the High Energy Arcing Faults (HEAF) has significant thermal damage to its surroundings. In this study, a chemical reaction model of Cu vapor to CuO particles by oxidation was developed to investigate the effect of the thermal radiation and adopted to a thermal fluid analysis with Ansys Fluent.